The motor reports ERR06 Motor Stall and the door stops moving. How do I fix this?
Background / Cause:
This fault occurs when the motor cannot rotate despite receiving power, indicating the controller has detected no movement feedback. Common causes include mechanical jamming, excessive load, brake failure to release, or motor winding damage.
Solutions:
1.Check for mechanical obstruction or bindingInspect the door track, rollers, and curtain for debris, misalignment, or physical jamming. Ensure the door moves smoothly when operated manually.
2.Verify brake release operationRun the motor in Jog mode and listen for the brake release click. If the brake does not release, follow the ERR05 troubleshooting steps to resolve brake issues.
3.Reduce load and check door balanceConfirm the door weight is within the motor’s rated capacity. Check counterbalance springs or weights to ensure they are properly adjusted.
4.Inspect motor wiring and windingCheck the motor power cable for damage or loose connections. Measure the three-phase winding resistance; unbalanced values indicate a damaged motor.
5.Adjust speed and acceleration parametersIf the fault occurs during start-up, reduce the initial speed or increase the acceleration time in the controller settings.
Notes:
• Repeated operation under stall conditions can cause permanent motor overheating and damage.
• Always resolve mechanical issues before attempting to reset the fault or adjust parameters.
-
The motor shows ERR04 System Overvoltage and stops running. How do I resolve this?
Background / Cause:
This fault occurs when the controller detects the DC bus voltage exceeds the safety threshold. Common causes include unstable/over-high input voltage, grid interference from high-power equipment, or a faulty controller voltage detection circuit.
Solutions:
1.Check the input power supplyMeasure the AC input voltage to confirm it is within the rated range of the controller. Fluctuations above 10% of the rated voltage will trigger this fault.
2.Reduce grid interferenceIf high-power equipment (such as welding machines or large motors) is sharing the same power circuit, move the door motor to an independent circuit or install a line filter to eliminate interference.
3.Verify the controller hardwareIf the input voltage is normal, the fault may be caused by a damaged voltage detection circuit inside the controller. Swap with a known working unit to test.
4.Check regenerative voltage (for high-speed doors)For fast-closing doors, check if the motor generates excessive regenerative voltage during deceleration. If so, adjust the deceleration parameters or add a braking resistor.
Notes:
• Do not repeatedly reset the fault without resolving the root cause, as sustained overvoltage can permanently damage the controller’s power components.
• Always confirm the power supply is stable before powering the system back on.
-
Controller shows ERR09 position learning failure, unable to finish stroke learning. How to fix?
Background / Cause:
System fails to record opening and closing limit positions normally. Caused by wrong limit signal, stuck door body, wrong parameters or encoder exception.
Solutions:
1.Check open and close limit switches and wiring, ensure signals respond normally.
2.Manually push the door to confirm it moves smoothly without jamming.
3.Restore factory settings, reset relevant running parameters.
Confirm encoder connection is firm, then redo position learning again.
Notes:
Only correct limit signals and smooth movement can complete learning successfully.
-
Controller displays ERR23 electronic travel not configured, door cannot run normally. How to solve?
Background / Cause:
No opening and closing stroke data is saved in the system, electronic travel has not been set up completely.
Solutions:
1.Enter parameter menu and start electronic stroke learning process.
2.Let the door automatically complete full open and full close travel calibration.
3.Check limit signals are normal before learning.
4.Save settings and restart after travel learning finished.
Notes:
All running functions are unavailable without completed travel configuration.
-
ERR16 motor overload protection appears, the door stops running automatically. How to deal with it?
Cause:
Motor load exceeds standard, current is too high, system triggers overload protection.
Solutions:
1.Check door body, track and rollers for stuck, friction and blockage.
2.Adjust balance spring to lighten motor load.
3.Reduce running speed and avoid frequent start and stop.
4.Stop use and cool down, clear fault then restart.
Notes:
Long time overload will burn out motor and circuit board.
-
Controller shows ERR27 system overheating and stops operation. How to solve?
Background / Cause:
Control box internal temperature exceeds safe value, triggered high temperature protection. Mainly caused by poor heat dissipation, long-time continuous operation, high ambient temperature or frequent heavy-load running.
Solutions:
1.Cut off power immediately and let the device fully cool down.
2.Keep control box ventilated, avoid sealed installation and sun exposure.
3.Reduce continuous working time and frequent opening & closing.
4.Check mechanical jamming leading to heavy load and heat generation.
Notes:
Do not force start after overheating, easy to burn internal electronic components.